Measured in the laboratoryUnderfloor heating integrated

Timber joist floor with wet screed, underfloor heating and suspended ceiling

System designation BHG_ZE_Messaufbau_F

Build-up from the top 50 ZE/20 MiWo/50 EPS/12,5 ST Tri

Tested floor build-up on a timber joist floor. In the laboratory, the assembly achieves a weighted normalised impact sound pressure level of 41 dB and a weighted sound reduction index of 79 dB. On the underside, a ceiling lining (direct resilient hangers / profiles) adds to the sound insulation.

Section drawing · dimensions in mm
41dB
Impact sound Ln,wCI = 2 dB · laboratory
79dB
Airborne sound RwLaboratory
531mm
Total build-upincluding the structural floor
186.5kg/m²
Mass per unit areaTotal build-up
DIN 4102-4
Fire resistance from belowfrom above: F90-B
Bestseller for concrete floor slabs
Wolf Bavaria system assembly

The assembly layer by layer

Section drawing and isometric view of the tested assembly BHG_ZE_Messaufbau_F, with all layer thicknesses. Select a layer in the drawing, the legend or the layer list to see its function.

Build-up height Impact sound Ln,w = 41 dBAirborne sound Rw = 79 dBWet screedValues according to the test report
Tip: use ↑ ↓ to step through the layers
ItemLayerThickness [mm]
In brief

Key facts at a glance

  • Tested: Impact sound Ln,w = 41 dB and airborne sound Rw = 79 dB in the laboratory, documented in the test report.
  • With wet screed: floating screed on tested impact sound insulation.
  • 531 mm total build-up including the structural floor.
  • All documents free of charge: Section drawing, test report, specification text and data sheets as PDFs by email.

Request planning documents

Explainer video · 1:40

System assemblies explained in 100 seconds

Architect Tina designs, developer Thorsten needs the evidence, building physicist Patrick checks it. Markus Schramm shows why our system assemblies are already tested and how our technical application team supports you with your own assemblies.

Ask a technical question
Explainer video thumbnail, system assemblies: over 50 tested assemblies 1:40

The video is only loaded from YouTube when you play it.

For your design

What this assembly means for you

Designers, tradespeople and developers look at different details. Choose who you are.

Design
Installation
Build and buy
Cartoon figure of architects

Design

Architects

What do I need to know for design and tendering?

  • 531 mm total build-upIncluding the structural floor. Mass per unit area 186.5 kg/m².
  • Fire resistanceFrom above F90-B, from below DIN 4102-4.
  • Ceiling liningDirect resilient hangers / profiles.
  • Use categoryA1–B2.
  • Ready for tenderItem-by-item specification text for all layers, matching the tested assembly.
Technical data

All performance values at a glance

The values are taken from the test report. They apply to the laboratory test rig without flanking transmission; values in the building depend on the junctions.

System designation
BHG_ZE_Messaufbau_F
Build-up from the top
50 ZE/20 MiWo/50 EPS/12,5 ST Tri
Floor type
Timber joist floor
Screed
Wet screed
Ceiling lining
Direct resilient hangers / profiles
Underfloor heating
integrated in the assembly
Screed
50 mm cement screed, m’ = 120 kg/m²
Insulation board
20 mm mineral wool impact sound insulation boards, m’ = 1.2 kg/m²
Insulation board
50 mm EPS thermal insulation boards, m’ = 0.94 kg/m²
Weighting layer
12.5 mm PhoneStar ST Tri acoustic boards, m’ = 18.0 kg/m²
Sheathing
19 mm P7 chipboard, m’ = 13.4 kg/m²
Structure
240 mm structural solid timber, e = 625 mm
Insulation
100 mm mineral wool insulation roll, ρ = 14 kg/m³
Substructure
127 mm direct resilient hangers with sheet steel profiles, e = 400 mm
Ceiling lining board
12.5 mm fire-rated plasterboard, m’ = 10.2 kg/m²
Weighted normalised impact sound pressure level
Ln,w (CI) = 41 (2) dB
Weighted sound reduction index
Rw = 79 dB (C; Ctr = -7; -15 dB)
Mass per unit area
186.5 kg/m²
Total build-up thickness
531 mm
Use category
A1–B2
Fire resistance from above
F90-B
Fire resistance from below
DIN 4102-4
Test evidence
Test report 19-002453-PR02 PB X07-F03-04-de-01
Manufacturer
Wolf Bavaria GmbH, Heilsbronn

Good to know

Need a different assembly? If none of our tested assemblies fits, our technical application team will work with you and our partners to develop a bespoke assembly and have it tested.

On-site values depend on flanking paths, junctions and penetrations. On request, we can measure the sound insulation in the laboratory or directly on site.

Load-bearing structure. The timber joists and the wood-based panel carry the structural loads. The bays, completely filled with porous fibrous insulation, damp the floor cavity and reduce resonances within the construction.

Variants

The BHG_ZE system family compared

Same structural floor, different screed and ceiling lining options. For impact sound, shorter bars mean a lower level; for airborne sound, longer bars mean better insulation.

VariantLn,wRwThickness
BHG_ZE_Messaufbau_HTimber joist floor32 dB82 dB544 mmView →BHG_ZE_Messaufbau_GTimber joist floor37 dB81 dB551 mmView →
BHG_ZE_Messaufbau_FTimber joist floor41 dB79 dB531 mmThis page

You will find all 55 floor assemblies, with filters and direct comparison, in the Assemblies overview →

Everything from a single source

Request design documents for this assembly

You will receive the complete package by email, tailored to this assembly. On request, our technical application team will contact you personally.

  • Test report 19-002453-PR02 PB X07-F03-04-de-01Cover sheet
  • ETA-20/0371 PhoneStar acoustic boards
  • Data sheet: PhoneStar ST Tri
  • Wolf MiWo data sheet
  • Installation instructions for Wolf Bavaria systems
  • Wolf system solutions specification text: timber joist floor
  • Personal consultationOur technical application team checks variants for your project
Markus Schramm, Wolf Bavaria, in productionMarkus Schramm as a cartoon character from the explainer video
“My team and I will be happy to help you personally with any technical questions. Please feel free to send us an enquiry.”

Markus SchrammM.Eng., Dipl.-Ing. (FH)
Head of Technical and Building Acoustics

Request documents

Assembly: BHG_ZE_Messaufbau_F