Timber joist floor with dry screed and ceiling on battens

System designation BHG 10.1 + DHG L 1.2

Build-up from the top 2x15 Tri/20 HFD/80 Splitt geb.

Tested floor build-up on a timber joist floor. In the laboratory, the assembly achieves a weighted normalised impact sound pressure level of 41 dB and a weighted sound reduction index of 78 dB. The assembly is installed completely dry, with no drying time. On the underside, a ceiling lining (battens) adds to the sound insulation.

Section drawing · dimensions in mm
41dB
Impact sound Ln,wCI = 2 dB · laboratory
78dB
Airborne sound RwLaboratory
441mm
Total build-upincluding the structural floor
250.1kg/m²
Mass per unit areaTotal build-up
F30-B
Fire resistance from belowfrom above: unclassified
Bestseller for concrete floor slabs
Wolf Bavaria system assembly

The assembly layer by layer

Section drawing and isometric view of the tested assembly BHG 10.1 + DHG L 1.2, with all layer thicknesses. Select a layer in the drawing, the legend or the layer list to see its function.

Build-up height Impact sound Ln,w = 41 dBAirborne sound Rw = 78 dBDry screedValues according to the test report
Tip: use ↑ ↓ to step through the layers
ItemLayerThickness [mm]
In brief

Key facts at a glance

  • Tested: Impact sound Ln,w = 41 dB and airborne sound Rw = 78 dB in the laboratory, documented in the test report.
  • Dry installation: no drying time, so the following trades can start promptly.
  • 441 mm total build-up including the structural floor.
  • All documents free of charge: Section drawing, test report, specification text and data sheets as PDFs by email.

Request planning documents

Explainer video · 1:40

System assemblies explained in 100 seconds

Architect Tina designs, developer Thorsten needs the evidence, building physicist Patrick checks it. Markus Schramm shows why our system assemblies are already tested and how our technical application team supports you with your own assemblies.

Ask a technical question
Explainer video thumbnail, system assemblies: over 50 tested assemblies 1:40

The video is only loaded from YouTube when you play it.

For your design

What this assembly means for you

Designers, tradespeople and developers look at different details. Choose who you are.

Design
Installation
Build and buy
Cartoon figure of architects

Design

Architects

What do I need to know for design and tendering?

  • 441 mm total build-upIncluding the structural floor. Mass per unit area 250.1 kg/m².
  • Fire resistanceFrom above: no classification; from below: F30-B.
  • Ceiling liningBattens.
  • Use categoryConsult the manufacturer.
  • Ready for tenderItem-by-item specification text for all layers, matching the tested assembly.
Technical data

All performance values at a glance

The values are taken from the test report. They apply to the laboratory test rig without flanking transmission; values in the building depend on the junctions.

System designation
BHG 10.1 + DHG L 1.2
Build-up from the top
2x15 Tri/20 HFD/80 Splitt geb.
Floor type
Timber joist floor
Screed
Dry screed
Ceiling lining
Battens
Screed
2 × 15 mm PhoneStar Tri sound insulation boards, m’ = 37.8 kg/m²
Insulation board
20 mm wood fibre insulation boards, m’ = 3.2 kg/m²
Fill
80 mm bonded grit fill, m’ = 131.9 kg/m²
Sheathing
22 mm wood-based panels, m’ = 13.3 kg/m²
Structure
240 mm structural solid timber, e = 508 mm
Insulation
2 × 120 mm mineral wool insulation, ρ = 20.6 kg/m³
Substructure
24 mm battens, e = 417 mm
Ceiling lining board
12.5 mm PhoneStar ST Tri sound insulation boards, m’ = 17.9 kg/m²
Ceiling lining board
12.5 mm fire-rated plasterboard, m’ = 12.9 kg/m²
Weighted normalised impact sound pressure level
Ln,w (CI) = 41 (2) dB
Weighted sound reduction index
Rw = 78 dB (C; Ctr = -5; -12 dB)
Mass per unit area
250.1 kg/m²
Total build-up thickness
441 mm
Use category
Coordinate with the manufacturer
Fire resistance from above
unclassified
Fire resistance from below
F30-B
Test evidence
Test report 17-001670-PR01 PB X25-F03-04-de-01_PB09
Manufacturer
Wolf Bavaria GmbH, Heilsbronn

Good to know

Need a different assembly? If none of our tested assemblies fits, our technical application team will work with you and our partners to develop a bespoke assembly and have it tested.

On-site values depend on flanking paths, junctions and penetrations. On request, we can measure the sound insulation in the laboratory or directly on site.

Load-bearing structure. The timber joists and the wood-based panel carry the structural loads. The bays, completely filled with porous fibrous insulation, damp the floor cavity and reduce resonances within the construction.

Ceiling lining with PhoneStar. Compared with a ceiling lining clad with plasterboard alone, the additional PhoneStar layer improves the normalised impact sound pressure level in the laboratory by up to 15 dB. Even higher sound insulation values can be achieved with a resiliently suspended ceiling, allowing a further improvement of 10 dB.

Variants

Similar assemblies: timber joist floor

Assemblies on the same floor type with comparable ratings. For impact sound, shorter bars mean a lower level; for airborne sound, longer bars mean more insulation.

You will find all 55 floor assemblies, with filters and direct comparison, in the Assemblies overview →

Everything from a single source

Request design documents for this assembly

You will receive the complete package by email, tailored to this assembly. On request, our technical application team will contact you personally.

  • Test report 17-001670-PR01 PB X25-F03-04-de-01_PB09Cover sheet
  • ETA-20/0371 PhoneStar acoustic boards
  • Data sheet: PhoneStar ST Tri
  • PhoneStar Tri data sheet
  • Data sheet: Wolf wood fibre insulation board
  • Limestone grit fill data sheet
  • Installation instructions for Wolf Bavaria systems
  • Wolf system solutions specification text: timber joist floor
  • Expert opinion, test series 17-001670
  • Personal consultationOur technical application team checks variants for your project
Markus Schramm, Wolf Bavaria, in productionMarkus Schramm as a cartoon character from the explainer video
“My team and I will be happy to help you personally with any technical questions. Please feel free to send us an enquiry.”

Markus SchrammM.Eng., Dipl.-Ing. (FH)
Head of Technical and Building Acoustics

Request documents

Assembly: BHG 10.1 + DHG L 1.2