Sound insulation in modular construction covers the measures used to design and join prefabricated volumetric modules so that the airborne and impact sound requirements between neighbouring units are met. The basic principle is the acoustic separation of the modules: double floors and walls, resilient bearings and joints without rigid connections.
- Between two modules, double elements are created automatically. Used correctly, they are a major acoustic advantage.
- The modules may only touch via defined, resilient bearings. Every rigid contact is a sound bridge.
- Low-frequency impact sound is the biggest challenge with lightweight timber floors. Mass in the floor build-up helps.
- Factory prefabrication allows reproducible quality, provided the details are tested and documented.
- Joints must be fire-rated, airtight and acoustically decoupled all at once.
The principle of sound insulation in modular construction: separating modules acoustically
In modular construction, finished volumetric units are produced in the factory, then stacked and placed side by side on site. Wherever two modules meet, there are automatically two elements above or next to each other: the ceiling of the lower module and the floor of the upper one, or the walls of two neighbouring modules. Acoustically, this is a great opportunity. Two separate leaves with an air gap between them form a twin-leaf element which, following the mass-spring-mass principle, insulates much better than a single leaf of the same mass.

The precondition: the two leaves may only touch where this is structurally necessary, and at those points they must sit on resilient bearings. Otherwise sound bridges turn the double leaf back into a single, rigidly connected element.
Double floor: module floor and module ceiling
The horizontal joint between two stacked modules is decisive for impact sound. The floor of the upper module carries a floating or decoupled floor build-up. Below that is an air gap, ideally with cavity damping, followed by the ceiling of the lower module. With lightweight timber structures in particular, the low frequencies of footfall noise determine how quiet the floor is perceived to be. Mass in the floor build-up, for example from heavy dry screed boards, noticeably improves this range. The BBSR report also points out that bathroom pods on cross-laminated timber floors need additional weighting of the structural floor.
Resilient bearings
The modules sit on bearings at corners, posts or along wall lines. These bearings are the direct connection between the leaves and therefore the most important structure-borne sound path. Resilient bearings interrupt it. A research report on timber modular construction by the German Federal Institute for Research on Building, Urban Affairs and Spatial Development (BBSR) shows that, as point or strip bearings, they also reduce the coupling length and are therefore highly effective, whereas rigid fixings significantly impair the decoupling. However, the bearings must be designed for the actual load: if underloaded they remain stiff, if overloaded they lose their effect. Our article What is acoustic decoupling? explains how decoupling works at junctions.
Double wall between neighbouring modules
A twin-leaf wall is formed between two modules standing side by side. The air gap between the leaves should be continuous and must not be bridged by installation aids, connecting plates or mortar. Fibrous insulation in the cavity damps cavity resonances. An additional lining with a high mass per unit area improves airborne sound insulation without making the wall noticeably thicker.
Joints, fire protection and services
The joints between modules have to fulfil three tasks at once: they must stop smoke and fire, be airtight and yet create no rigid connection. Soft, non-combustible joint fillers and sealing tapes coordinated with the fire strategy have proven effective. Services running from module to module need flexible transitions and resilient fixings, otherwise they carry structure-borne sound from one unit into the next.
The prefabrication advantage: factory quality
In the factory, build-ups, connections and decoupling details can be produced and checked under consistent conditions, regardless of the weather. This is a real advantage for sound insulation, because many defects on site result from small workmanship errors. It is important that the details are available as tested systems and that critical points such as bearings and joints are documented during assembly.
- Install the floor build-up and decoupling in the factory.
- Position bearings according to the load plan and check them before setting the module down.
- Close joints after placing the modules, without rigid filling.
- Plan building services penetrations and transitions in advance.
Which values apply?
Modular buildings are subject to the same requirements as any other building. In Germany, DIN 4109-1 requires R′w ≥ 53 dB for separating walls between flats in apartment buildings, R′w ≥ 54 dB for separating floors and an impact sound level of L′n,w ≤ 50 dB. For floors in timber, lightweight and drywall construction to DIN 4109-33, L′n,w ≤ 53 dB is permitted. DIN 4109-1 contains separate tables for hotels, hospitals and schools. Find out more in DIN 4109 explained. In England and Wales, Approved Document E applies to modular buildings in exactly the same way as to conventionally built ones.
Case studies
- Prefabricated house, factory-built: at Keitel-Haus, PhoneStrip and PhoneStar were installed in the factory. According to the case study page, the measured values were R′w 60 dB for the wall and R′w 68 dB and L′n,w 48 dB for the floor.
- Modular nursery: for KiTa Dudenhofen, with 11 modules and 445 m², the module walls were lined with PhoneStar ST Tri between plasterboard and OSB.
Frequently asked questions
Not necessarily. Because double floors and walls are created automatically between two modules, modular buildings can achieve very good values. The prerequisites are resilient bearings, continuous air gaps and joints without rigid connections.
Usually the bearings and joints between the modules. Every rigid connection, such as an installation bracket or a mortar joint, forms a sound bridge and transmits structure-borne sound directly from module to module.
Lightweight timber floors transmit low-frequency footfall noise more readily than heavy concrete slabs. Mass in the floor build-up and good decoupling between module floor and module ceiling improve this range.
The same as for all buildings. In Germany these are the minimum requirements of DIN 4109-1: for flats, for example, 53 dB for separating walls, 54 dB for separating floors and an impact sound level of no more than 50 dB, or no more than 53 dB for timber floors to DIN 4109-33. In England and Wales, Approved Document E applies.
Through tested system build-ups, fixed work instructions for bearings and joints, and documentation of the critical details. Sound insulation can also be measured in the completed building.
Sources
- DIN 4109-1:2018-01 Sound insulation in buildings, Part 1: Minimum requirements. DIN Media.
- DIN 4109-33:2016-07 Sound insulation in buildings, Part 33: Data for verification of sound insulation by calculation (component catalogue), timber, lightweight and drywall construction. DIN Media.
- DIN EN ISO 12354-1:2017-11 and DIN EN ISO 12354-2:2017-11 Estimation of acoustic performance of buildings from the performance of elements. DIN Media.
- Rabold et al.: Schallschutz von Gebäuden in Holzmodulbauweise, Federal Institute for Research on Building, Urban Affairs and Spatial Development (BBSR), Zukunft Bau Forschung Kompakt 16/2025, Bonn 2026.
- Wolf Bavaria: Keitel-Haus and KiTa Dudenhofen case studies.