Retrofit underfloor heating: dry, low profile, no screed drying time

Retrofit underfloor heating in an older building without waiting weeks for screed to dry. Dry systems add only a few centimetres and can be combined with impact sound insulation. We explain the build-up, planning and what matters with a heat pump.
Reading time: approx. 8 minExpert knowledge from Wolf Bavaria
Grafik Trockenbau-Fußbodenheizung: Heizrohr in Mäanderform auf Wärmeleitblechen mit 20 mm Aufbauhöhe
In brief

Dry underfloor heating is a surface heating system in which the heating pipes sit in prefabricated system panels with heat diffuser plates instead of being cast into a wet screed. A dry screed or the floor finish goes directly on top. These systems are low profile, respond quickly and make it possible to retrofit underfloor heating without any drying time, including on timber joist floors.

Key facts
  • EN 1264 (BS EN 1264 in the UK) distinguishes between system types: pipes embedded in screed are types A, C, H, I and J, while pipes below the screed or timber floor are type B.
  • Dry systems need only a few centimetres of build-up height. PowerFloor, for example, has a build-up of 20 to 30 mm.
  • Less mass means a faster response: the room warms up quickly and the heating is easy to control.
  • Low flow temperatures improve heat pump efficiency. Underfloor heating helps, but it is not essential in every case.
  • For comfort, surface temperature limits apply: 29 °C in the occupied zone and 35 °C in perimeter zones.

Wet or dry: the system types

In conventional underfloor heating, the pipes are embedded in a cement or calcium sulphate screed. The screed stores a lot of heat, but it takes weeks to dry and needs a commissioning heat-up protocol before the floor finish can be laid. EN 1264 classifies such systems as types A, C, H, I and J. In type B, by contrast, the pipes run below the screed or timber floor, usually in system panels with heat diffuser plates. This is the family that dry underfloor heating systems belong to.

Section through dry underfloor heating: floor finish, dry screed, heat diffuser plate, honeycomb panel with heating pipe and PowerFloor performance data
Build-up of a dry underfloor heating system with PowerFloor performance data.

Why retrofit underfloor heating works best as a dry system

  • Low build-up height: in older buildings every millimetre counts. Dry systems add only a few centimetres.
  • Low weight: old timber joist floors have little spare load capacity. According to the product page, the PowerFloor Light panel weighs around 2.1 kg/m².
  • No construction moisture: no water gets into joists and floorboards, and there is no waiting time before the floor finish can be laid.
  • Fast response: because there is little mass to heat up, the room temperature follows the controls quickly.
  • Floor, wall and ceiling: many dry systems can also be installed on walls and ceilings.

Underfloor heating and heat pumps

Heat pumps work more efficiently the lower the required flow temperature. Underfloor and other surface heating systems emit heat over a large area and can therefore run on low flow temperatures. In a field test of heat pumps in existing buildings, Fraunhofer ISE measured seasonal performance factors of 2.5 to 3.8 for air source heat pumps and 3.3 to 4.7 for ground source heat pumps, with an average maximum required flow temperature of just under 44 °C. The researchers also stress, however, that surface heating is not necessarily required: what matters is the heating circuit temperature actually needed. A heat loss calculation and hydraulic balancing should therefore come at the start of any design.

How warm can the floor get?

When designing underfloor heating to EN 1264, physiological limits for the surface temperature apply: 29 °C in the occupied zone, 35 °C in perimeter zones and, in bathrooms, room temperature plus 9 K, i.e. around 33 °C. For the heat to reach the room, the floor covering should have the lowest possible thermal resistance. Tiles and stone conduct heat well, while thick carpets and timber floor finishes slow it down more.

Cooling is possible too

Surface systems can also cool when supplied with cold water. For PowerFloor, the product page states a cooling output at a temperature difference of 8 K of up to 31 W/m² on the floor, 41 W/m² on the wall and 37 W/m² on the ceiling. When cooling, the flow temperature must be controlled so that no condensation forms on the surfaces.

Combining underfloor heating with sound insulation

Dry underfloor heating can be integrated into an acoustically effective floor build-up. The key point is that the heating, dry screed and impact sound insulation have been tested together as a system. For build-ups with PowerFloor and PhoneStar on solid timber floors, the product page gives the following test results, among others:

Build-upTotal thicknessAirborne soundImpact sound
Solid timber floor with resilient hangers393 mmRw 75 dBLn,w 28 dB
Solid timber floor, loose fill and mineral wool315 mmRw 72 dBΔLn,w 37 dB
Solid timber floor and mineral wool255 mmRw 66 dBΔLn,w 27 dB

Here, ΔLn,w denotes the difference between the normalised impact sound pressure levels with and without the build-up on the tested solid timber floor. The values apply to exactly this overall build-up. They are not comparable with the impact sound reduction ΔLw on a standard reference floor and cannot be derived from individual product values. In the UK, the performance of separating floors is assessed under Approved Document E, with single-number ratings to BS EN ISO 717.

PowerFloor in figures

  • Build-up height 20 to 30 mm, 30 mm on walls and ceilings
  • Honeycomb board with milled pipe channels and aluminium heat diffuser plate
  • PE-RT/aluminium multilayer pipe 16 × 2.0 mm, pipe spacing 125 mm
  • Compressive strength 500 kPa across the full surface right up to the edge
  • Suitable for heat pumps and solar thermal systems, and can also be connected to existing heating with a fixed-temperature control set
  • Installation from 10 °C at 30 to 60 per cent relative humidity

Planning your retrofit underfloor heating step by step

  1. Have a room-by-room heat loss calculation carried out.
  2. Check the available build-up height and the floor’s spare load capacity.
  3. Choose the floor covering and take its thermal resistance into account.
  4. Draw up a layout plan with heating circuits, manifold and pipe routes.
  5. Plan sound insulation and impact sound insulation as one overall system.
  6. After installation, carry out a pressure test, hydraulic balancing and set up the controls.
Find out more

You will find details of the system on the PowerFloor surface heating product page. Our farmhouse loft conversion case study shows how a loft conversion with dry underfloor heating and impact sound insulation was completed as a self-build project.

Frequently asked questions

How much height does dry underfloor heating add?

Dry systems usually add only a few centimetres. PowerFloor panels are 20, 24 or 30 mm thick. Depending on the build-up, dry screed, floor finish and, where needed, impact sound insulation are added on top.

Can you retrofit underfloor heating without screed?

Yes. In dry systems the pipes sit in system panels with heat diffuser plates, topped by a dry screed or directly by a suitable floor finish. There is no construction moisture and no drying time.

Is underfloor heating with a heat pump worthwhile in an older building?

Often, yes, because surface heating systems run on low flow temperatures and heat pumps then work more efficiently. Field tests by Fraunhofer ISE show, however, that heat pumps in existing buildings can also work without surface heating. What matters is the flow temperature actually required.

How warm can the surface of underfloor heating get?

Under EN 1264 the limits are 29 °C in the occupied zone, 35 °C in perimeter zones and around 33 °C in bathrooms.

Can underfloor heating be used for cooling?

Yes, if the system and the heat source are designed for it. The flow temperature must be controlled so that no condensation forms on the surfaces.

Which floor covering suits underfloor heating?

Ideally coverings with low thermal resistance, such as tiles, natural stone, vinyl or thin parquet approved for underfloor heating. Thick carpets and timber floor finishes insulate more and slow down heat output.

Sources

  1. DIN EN 1264-1:2021-08 Water based surface embedded heating and cooling systems, Part 1: Definitions and symbols. DIN Media.
  2. DIN EN 1264-2:2021-08 Water based surface embedded heating and cooling systems, Part 2: Floor heating, methods for the determination of the thermal output. DIN Media.
  3. Fraunhofer Institute for Solar Energy Systems ISE: press release WPsmart im Bestand, 27 July 2020.
  4. Fraunhofer Institute for Solar Energy Systems ISE: news item on the WP-QS project, 1 March 2024.
  5. Wolf Bavaria: PowerFloor surface heating product page with test results and technical data.