DIN 4109 “Sound insulation in buildings” is the German series of standards for sound insulation in construction. Part 1 (2018-01 edition) sets the minimum requirements for airborne and impact sound insulation required under building regulations, Part 2 describes verification by calculation, Parts 31 to 36 provide the component data, Part 4 covers testing and Part 5 (2020-08) defines enhanced requirements that can be agreed by contract. It is broadly comparable in role to Approved Document E in England and Wales or CTE DB-HR in Spain.
- The governing requirements standard is DIN 4109-1:2018-01. It is adopted into building regulations through the federal states’ technical building rules.
- Between dwellings: wall R′w ≥ 53 dB, floor R′w ≥ 54 dB and L′n,w ≤ 50 dB. For floors in timber, lightweight and drylining construction to DIN 4109-33, L′n,w ≤ 53 dB is permitted.
- Verification is by calculation to DIN 4109-2, with an allowance for prediction uncertainty uprog of 2 dB for airborne sound and 3 dB for impact sound.
- Enhanced sound insulation to DIN 4109-5 only applies if it has been agreed, for example separating floor R′w ≥ 57 dB and L′n,w ≤ 45 dB.
- According to the German Federal Court of Justice (BGH), the minimum values of DIN 4109 do not describe the usual level of comfort. Anyone expecting more should agree specific values.
What does DIN 4109 apply to?
DIN 4109 protects people in habitable rooms from unreasonable disturbance by sound. It sets requirements for airborne and impact sound insulation between separate residential and working units, for protection against external noise via the facade, windows and roof, and for noise from building services such as lifts or sanitary installations.
The standard protects so-called noise-sensitive rooms. These include living rooms and kitchen-diners, bedrooms, children’s rooms, hospital wards, classrooms as well as offices, consulting rooms and meeting rooms. Kitchens without a living function, bathrooms, hallways and storerooms, on the other hand, are not considered noise-sensitive in the sense of the standard.
The requirements apply between separate units, i.e. between two flats, between a flat and a stairwell or between terraced houses. DIN 4109-1 sets no requirements for sound insulation within your own flat or house. Recommendations for this can be found in VDI 4100, for example.
The parts of DIN 4109 at a glance
The former DIN 4109 of 1989 with its supplements has been replaced by a series of standards. Its structure is logical: one part says what applies, one part says how to verify it, and several parts provide the data for this.

| Part | Content | Role in practice |
|---|---|---|
| DIN 4109-1 | Minimum requirements | Required values per building element and building type, adopted into building regulations |
| DIN 4109-2 | Verification by calculation | Prediction method for airborne and impact sound including flanking transmission |
| DIN 4109-31 | Framework document | Principles and structure of the component catalogue |
| DIN 4109-32 | Masonry and concrete construction | Input data for concrete and masonry walls and floors |
| DIN 4109-33 | Timber, lightweight and drylining construction | Input data for timber joist, timber-concrete composite and drylining constructions |
| DIN 4109-34 | Linings | Independent linings in front of solid building elements |
| DIN 4109-35 | Elements, windows, doors, curtain walls | Input data for building components |
| DIN 4109-36 | Building services | Data on noise from building services |
| DIN 4109-4 | Building acoustics testing | Test methods and suitability tests |
| DIN 4109-5 | Enhanced requirements (2020-08) | Higher values, binding only if agreed by contract |
Since August 2026, the drafts E DIN 4109-2:2026-09 and E DIN 4109-33:2026-09 have been available. Drafts are not yet to be applied, but they show where the verification method and the component catalogue for timber construction are heading. Which editions apply under building regulations in each German federal state is governed by the respective administrative regulation on technical building rules, based on the MVV TB of the DIBt.
Minimum requirements to DIN 4109-1: the key values
The most common question is: what is the minimum sound insulation between flats? The answer is in Table 2 of DIN 4109-1. Separating walls between flats require a weighted apparent sound reduction index of R′w ≥ 53 dB, separating floors R′w ≥ 54 dB and a maximum permitted weighted normalised impact sound pressure level of L′n,w ≤ 50 dB.

Blocks of flats and mixed-use buildings (extract from Table 2)
| Building element | req. R′w | max. L′n,w |
|---|---|---|
| Separating floors between flats | 54 dB | 50 dB ¹ ² |
| Separating walls between flats | 53 dB | – |
| Stairwell walls | 53 dB | – |
| Stair flights and landings | – | 53 dB |
¹ For alterations to buildings completed before 1 July 2016, L′n,w ≤ 53 dB applies. ² For floors in timber, lightweight and drylining construction to DIN 4109-33, L′n,w ≤ 53 dB applies.
Terraced and semi-detached houses (extract from Table 3)
| Building element | req. R′w | max. L′n,w |
|---|---|---|
| Party wall to habitable rooms on the lowest storey | 59 dB | – |
| Party wall with at least one storey below | 62 dB | – |
| Floors | – | 41 dB |
| Ground slab or floor above basement | – | 46 dB |
| Stairs | – | 46 dB |
A simple rule helps when reading the values: for airborne sound a higher R′w is better, for impact sound a lower L′n,w. The prime on the symbol means it is a value in the installed condition, i.e. including transmission via flanking elements. Note that Approved Document E uses different on-site quantities (DnT,w + Ctr and L′nT,w), so its figures cannot be compared directly with DIN 4109. Find out more about the ratings in What is sound insulation?.
Verification to DIN 4109-2
Whether a building element meets the requirement is verified by calculation at the design stage. DIN 4109-2 describes a prediction method that takes into account not only the direct path through the separating element but also the flanking paths via adjoining walls, floors and facades. Between two rooms, besides the direct path, there are up to twelve flanking paths via the four junctions.
Where do the input data come from?
The sound insulation of the individual elements comes either from the component catalogue DIN 4109-31 to 36 or from test certificates and measurements to the test standards. For constructions not listed in the catalogue, such as new dry screed or floor systems, laboratory test values form the basis. A laboratory value Rw without a prime must not be confused with the field value R′w.
Prediction uncertainty: 2 dB and 3 dB
Because every prediction carries uncertainty, DIN 4109-2 includes a prediction uncertainty uprog, often called a safety factor in the literature. It is 2 dB for airborne sound and 3 dB for impact sound. The predicted value must therefore meet the requirement with a margin:
After completion, sound insulation can be measured on site. The measurement is carried out to DIN EN ISO 16283, and the single-number ratings are derived to DIN EN ISO 717-1 for airborne sound and DIN EN ISO 717-2 for impact sound. These are the same standards used in the UK as BS EN ISO 16283 and BS EN ISO 717 for pre-completion testing under Approved Document E.
Design with build-ups for which reliable test values are available. In our system build-ups you will find floor, wall and ceiling build-ups with measured laboratory values, including for timber joist floors and cross-laminated timber.
Enhanced sound insulation: DIN 4109-5, VDI 4100 and DEGA 103
DIN 4109-1 describes a minimum standard intended to protect against unreasonable disturbance. Normal speech from the neighbouring flat may still be audible. Anyone who wants more peace and quiet will find higher values in three sets of rules:
| Standard or guideline | What it specifies | Example: separating floor between flats |
|---|---|---|
| DIN 4109-5:2020-08 | Enhanced requirements, replaces Supplement 2 and DIN SPEC 91314 | R′w ≥ 57 dB, L′n,w ≤ 45 dB |
| VDI 4100:2012-10 | Three sound insulation levels SSt I to III for flats | DnT,w 56 / 59 / 64 dB, L′nT,w 51 / 44 / 37 dB |
| DEGA guideline 103-1:2024-09 | Sound insulation classes A* to F, class D essentially corresponds to DIN 4109-1 | Graded classes, basis for an acoustic performance certificate |
Under DIN 4109-5, requirements include R′w ≥ 56 dB for separating walls between flats and R′w ≥ 67 dB for party walls between houses, or 62 dB on the lowest storey. Note that VDI 4100 and DEGA use different quantities, the standardised level difference DnT,w and the standardised impact sound pressure level L′nT,w. They refer to the reverberation time in the receiving room and are not directly comparable with R′w.
What the German courts say
For clients and developers in Germany, one ruling of the Federal Court of Justice is central. In its judgment of 14 June 2007 (VII ZR 45/06), the BGH ruled that the sound reduction indices of DIN 4109 do not describe the usual standard of quality and comfort, because they merely set minimum requirements to avoid unreasonable disturbance. As reference points, the court cited the enhanced levels of VDI 4100 or the then Supplement 2. In its judgment of 4 June 2009 (VII ZR 54/07), the BGH clarified that a mere reference to “sound insulation to DIN 4109” in the contract does not automatically mean only the minimum values.
Specify the sound insulation in the contract precisely: quantity, numerical value and standard, for example “separating floors between flats R′w ≥ 57 dB and L′n,w ≤ 45 dB to DIN 4109-5”. This creates clarity for everyone involved. This article does not constitute legal advice.
DIN 4109 in practice: timber construction, drylining and refurbishment
Timber and modular construction
For floors to DIN 4109-33, the standard permits an impact sound level of up to 53 dB. This is a concession to lightweight constructions, but it does not solve the typical problem of low-frequency footstep noise. For timber joist floors and cross-laminated timber, it is worth also looking at the spectrum adaptation term CI,50-2500 and designing build-ups with high mass on the floor, good decoupling and decoupled junctions. The principles are explained in our article on the mass-spring-mass principle.
Refurbishment and alterations
Existing buildings often lack build-up height, and old timber joist floors have little spare load capacity. For alterations to buildings completed before 1 July 2016, DIN 4109-1 permits an impact sound level of L′n,w ≤ 53 dB. Slim dry build-ups help to achieve the values without moisture or drying time. Find out more on our page dry screed in refurbishment and in the dry screed calculator.
Frequently asked questions about DIN 4109
Yes. The governing document is the DIN 4109 series with the requirements standard DIN 4109-1 in the 2018-01 edition, which is adopted into building regulations. New drafts of DIN 4109-2 and DIN 4109-33 have been available since August 2026, but they do not yet apply.
Under DIN 4109-1, separating walls between flats require a weighted apparent sound reduction index of at least 53 dB, separating floors at least 54 dB. The impact sound level of separating floors may not exceed 50 dB, or 53 dB for floors in timber, lightweight and drylining construction to DIN 4109-33.
The minimum requirements of DIN 4109-1 are adopted into building regulations through the federal states’ technical building rules and are therefore binding in Germany. Enhanced requirements to DIN 4109-5 or VDI 4100 only apply if they are agreed by contract.
Under building regulations, DIN 4109-1 is binding. Under civil law, the BGH ruled in judgment VII ZR 45/06 that its minimum values do not describe the usual standard of quality and comfort. Without a specific agreement, a higher level of sound insulation may therefore be owed.
Noise-sensitive rooms are habitable rooms that must be protected against noise, including living rooms and kitchen-diners, bedrooms and children’s rooms, hospital wards, classrooms as well as offices, consulting rooms and meeting rooms. Bathrooms, hallways and storerooms are not included.
Enhanced sound insulation is covered by DIN 4109-5 of 2020. The values are above the minimum requirements, for example 57 dB instead of 54 dB for airborne sound insulation and 45 dB instead of 50 dB for impact sound of separating floors between flats. They only apply if they have been agreed.
DIN 4109 itself has no classes, only minimum and enhanced values. Graded levels are offered by VDI 4100 with sound insulation levels SSt I to III, and DEGA guideline 103-1 of 2024 defines classes from A* to F.
Sources
- DIN 4109-1:2018-01 Sound insulation in buildings, Part 1: Minimum requirements. DIN Media.
- DIN 4109-2:2018-01 Sound insulation in buildings, Part 2: Verification of compliance with the requirements by calculation. DIN Media.
- DIN 4109-5:2020-08 Sound insulation in buildings, Part 5: Enhanced requirements. DIN Media.
- E DIN 4109-2:2026-09 and E DIN 4109-33:2026-09, draft standards. DIN Media.
- Deutsches Institut für Bautechnik: Model Administrative Regulation on Technical Building Rules (MVV TB).
- VDI 4100:2012-10 Sound insulation in buildings, dwellings, assessment and proposals for enhanced sound insulation.
- DEGA guideline 103-1:2024-09 Sound insulation in residential buildings, sound insulation classes. German Acoustical Society.
- BGH, judgment of 14.06.2007, VII ZR 45/06, BGHZ 172, 346.
- BGH, judgment of 04.06.2009, VII ZR 54/07, BGHZ 181, 225.
- Holzbau Deutschland: press release on DIN 4109-5, 29.09.2020.
- Lärmkontor: The new DIN 4109:2018-01, presentation of 12.02.2021 (prediction uncertainty).


