Sound insulation solutions for solid concrete floors
The ‘Concrete slab’ best-seller is based on an extensive series of tests carried out by Wolf Bavaria and its partners. In the building acoustics laboratory at ift Rosenheim, more than 20 systematically varied dry screed systems were tested on a 160 mm-thick reinforced concrete slab.
Based on the measurements, the ift Rosenheim drew up an expert report containing a comprehensive evaluation matrix. Among other things, this report assessed various dry screeds, impact sound insulation boards, levelling fill materials and fill heights. The following statements are therefore based on measurement and test findings, and not on generalised assumptions.
1. Dry screed
1. Dry screed, load distribution, mass and underfloor heating
Components
18 mm Wolf HUGO GF prefabricated screed
20 mm Wolf PowerFloor Light
2 x 12.5 mm PhoneStar ST Tri
The 18 mm-thick Wolf HUGO gypsum fibre prefabricated board distributes the live loads and forms the load-bearing surface. The 20 mm-thick Wolf PowerFloor underfloor heating system enables a fast-responding heating system without additional construction moisture.
Two layers of PhoneStar ST Tri complement the structure, providing high mass and acoustic flexibility. The test series also shows that the PowerFloor structure, when installed correctly, does not impair sound insulation performance. The structure therefore performs effectively even without underfloor heating, with no reduction in performance.
2. Impact sound insulation
2. Mineral fibre impact sound insulation, effective decoupling
Components
12 mm Wolf MiWo 12-2, s’ ≤ 40 MN/m³
The 12 mm-thick Wolf MiWo 12-2 provides an elastic separation between the dry screed and the levelling fill. It acts as a central spring in the mass-spring-mass system and reduces the transmission of impact and footfall noise.
In general, softer mineral fibre impact sound insulation boards offer acoustic advantages. At the same time, compressibility, compressive strength and the permissible deflection of the overall structure must be taken into account. For the standard residential live load of 1.5 kN/m², a maximum permissible deflection of 3 mm applies. In the case of very soft insulation layers, additional edge and floor stabilisation using PhoneStar Schalli may be advisable.
3. Ausgleichsschüttung3. Compensation payment
3. Compensatory flow, level control and elastic behaviour
Components
30 mm Cemwood or perlite
On concrete and solid slabs, the dry fill primarily serves to level out the surface. Particularly in renovation work, uneven sub-floors, existing tolerances and service pipes must be transformed into a level base surface for the dry screed.
Unlike with timber floors, the priority here is not to achieve the greatest possible mass of the fill. Rather, what is decisive is its elastic behaviour, or rather the resulting dynamic stiffness of the entire structure. Even a small fill height can lower the resonance frequency of the floating floor and thereby significantly improve impact sound insulation in particular.
Cemwood and perlite have a proven track record and have undergone testing. With a fill height of 30 mm, both variants, in combination with the superstructure shown, achieve a rated standard impact sound level of Ln,w = 41 dB. Depending on the fill material, the rated sound reduction index ranges from Rw = 69 to 70 dB.
4, Tragkonstruktion4. Structural framework
4. Load-bearing structure: the concrete slab
Components
160 mm reinforced concrete floor slab
The tested load-bearing structure consists of a 160 mm-thick reinforced concrete floor slab with a mass per unit area of 382 kg/m². It already has a significantly higher inherent acoustic performance than a timber or solid timber floor.
The measurement and design values relate to this tested reference slab. For other slab thicknesses, bulk densities or structural connections, the applicability must be checked on a project-by-project basis. For thicker standard concrete slabs, an improvement of approximately 1 dB per centimetre of concrete thickness can be assumed.
5. Suspended ceiling
5. Suspended ceiling, optional design variant
For concrete ceilings, the test series described does not include any tests involving a suspended ceiling.
In terms of construction, the principles are generally similar to those for solid timber ceilings. However, as the heavy concrete ceiling already has a high baseline level of sound insulation, achieving further acoustic improvement is significantly more difficult and often less efficient.
If the suspended ceilings are poorly dimensioned, the additional air gap can create resonance and impair sound insulation in the low-frequency range. If a suspended ceiling is to be installed, it should therefore be designed with a generous suspension height of at least 120 mm and a suitable spring-loaded suspension system.
The suspension height, suspension points, cladding material and cavity insulation must be considered as a coordinated system. We would be happy to advise you on this matter.
Done.
Slim-line levelling. Dry construction method. Tested sound insulation.
The PhoneStar Top Seller concrete floor combines a compact levelling layer with effective impact sound decoupling, a high-density dry screed and a fast-responding underfloor heating system.
With a levelling layer of just 30 mm, the installation remains slim and is suitable for both new builds and refurbishments, without compromising on robust acoustic design parameters.
Practical floor construction
From experience, for practical use. Our products have been in use on construction sites around the world for over 22 years.
In 2024, we celebrated our 20th anniversary.