Impact sound insulation, often simply called acoustic floor insulation, is a resilient layer between the screed or floor covering and the structural floor. It decouples the floor from the slab so that footsteps and impacts do not travel unhindered as structure-borne sound into the construction and adjoining rooms. What determines its performance is a low dynamic stiffness s′ combined with sufficient load-bearing capacity.
- Under a screed, impact sound insulation is the spring in a mass-spring-mass system. The lower its dynamic stiffness s′, the better it decouples.
- Under the German standard DIN 4108-10, the application type for insulation under screed with acoustic requirements is called DES, supplemented by the compressibility class sh, sm or sg.
- On the data sheet, SD stands for the dynamic stiffness level and CP for compressibility, in other words the difference between the delivered thickness and the thickness under load.
- An underlay beneath laminate or parquet is not the same as impact sound insulation under screed and is assessed using its own performance values.
- Perimeter edge strips and a level substrate are just as important as the insulation material itself.
How acoustic floor insulation works
Impact sound is generated when a floor is excited mechanically, for example by footsteps, falling objects or chairs being moved. If the screed is rigidly bonded to the structural floor, this excitation travels unhindered into the slab and is radiated as airborne sound into the room below. Impact sound insulation separates the two layers. Together with the screed and the structural floor, it forms a vibrating system that transmits considerably less vibration above its resonance frequency. The physics behind this is explained in our article on the mass-spring-mass principle.
The softer the insulation layer, the lower the resonance frequency and the better the performance. At the same time, the insulation must permanently carry the loads from the screed, furniture and use without compressing too much. Selecting acoustic floor insulation is therefore always a balance between acoustic softness and load-bearing capacity.
Under the screed or under the floor covering
| Impact sound insulation under screed | Underlay beneath laminate or parquet | |
|---|---|---|
| Position | between the structural floor and the screed or dry screed | between the screed and a floating floor covering |
| Function | spring in the mass-spring-mass system, main contribution to impact sound insulation | improves impact sound and walking noise of the floor covering |
| Performance values | dynamic stiffness s′, compressibility, application type DES | ISLam for impact sound, RWSLam for walking noise in the room |
| Standards and guidance | DIN 4108-10, product standards EN 13162 ff. | technical leaflet of the Association of European Producers of Laminate Flooring (EPLF) |
An underlay beneath the floor covering cannot replace missing or poor impact sound insulation under the screed. According to the EPLF technical leaflet, a laminate underlay should achieve an ISLam of at least 14 dB, and 18 dB for higher requirements. These values are determined on a small test floor and cannot be compared with the impact sound reduction ΔLw of a screed.
The key values on an acoustic floor insulation data sheet

- Dynamic stiffness s′: the spring stiffness of the insulation per unit area in MN/m³, measured to EN 29052-1. On the label it appears as a level, for example SD20 for a maximum of 20 MN/m³. SD and CP are designation codes from the European product standards, so you will also find them on products sold in the UK, whereas DES is a German application code.
- Compressibility c: the difference between the delivered thickness dL and the thickness under load dB. CP3 means that the insulation compresses by no more than 3 mm. The packaging often states both, for example 25-5 for 25 mm delivered thickness and 20 mm thickness under load.
- Application type: DES for insulation under screed with acoustic requirements to DIN 4108-10, supplemented by sh (increased), sm (medium) or sg (low compressibility).
- Load-bearing capacity: the higher the imposed loads, the less the insulation may compress. For mineral wool of class sg and imposed loads above 5 kPa, DIN 4108-10 additionally requires proof of creep behaviour.
- Reaction to fire and thermal conductivity: important if the insulation also has thermal or fire protection functions.
Acoustic floor insulation materials compared
Three groups of insulation materials are mainly used for impact sound insulation under screed. Which one is suitable depends on the load, build-up height, type of screed and other requirements.
| Insulation material | Typical properties | Note |
|---|---|---|
| Mineral wool (MW) | very low dynamic stiffness possible, good impact sound performance | pay attention to compressibility and load |
| Elasticised polystyrene (EPS) | lightweight, easy to work with | only elasticised types are suitable for impact sound |
| Wood fibre (WF) | higher compressive strength, renewable raw material | DIN 4108-10 defines classes sh and sg, usually higher s′ |
The values of the specific product are always what counts. Two boards made of the same material can differ considerably in dynamic stiffness and load-bearing capacity.
How much does impact sound insulation achieve?
The performance of a floor topping is stated as the weighted reduction in impact sound pressure level ΔLw. It is measured to EN ISO 10140-3 on a standardised concrete floor and rated to EN ISO 717-2 (published in the UK as BS EN ISO 717-2). According to older tabulated values, a floating cement screed on a soft insulation layer with a dynamic stiffness below 10 MN/m³ achieves an impact sound reduction of around 30 dB.
In timber construction, the entire floor build-up counts, not the individual value of one product. On a solid timber floor, tested build-ups with PhoneStar dry screed and PowerFloor radiant heating improve the normalised impact sound pressure level, according to the product page, by 27 dB on mineral wool and by 37 dB with additional loose fill, for example. These differences apply to exactly this floor and this build-up. They cannot be compared with ΔLw on the standardised concrete floor and cannot be transferred to other floors. In England and Wales, the impact sound performance of separating floors is assessed against Approved Document E, which looks at the complete floor as built rather than at individual layers.
Typical mistakes with impact sound insulation
- Perimeter edge strips are missing or trimmed too early, so the screed touches the wall.
- Pipes lie on the structural floor without a levelling layer, so the insulation is not fully supported and breaks.
- Insulation that is too soft is used under a dry screed. Dry screed systems usually require insulation layers with low compressibility; the manufacturer’s specification is decisive.
- With multi-layer installation, the joints are placed on top of each other instead of staggered.
- Two underlays are stacked beneath the floor covering instead of choosing one suitable underlay.
Plan impact sound insulation and screed as a system. Our system build-ups include tested combinations of insulation, PhoneStar dry screed and floor covering with measured values. You can read more about dry screed in What is dry screed?.
Frequently asked questions about acoustic floor insulation
There is no single best impact sound insulation. What matters is a low dynamic stiffness for acoustic performance and suitable load-bearing capacity for the screed and the intended use. Mineral wool often achieves the lowest stiffness values, wood fibre has higher compressive strength and elasticised EPS is lightweight. The values of the specific product are decisive.
SD indicates the dynamic stiffness level; SD20, for example, means a maximum of 20 MN/m³. CP indicates compressibility; CP3 means that the insulation compresses by no more than 3 mm under load.
Under DIN 4108-10, DES is the application type for insulation under screed with acoustic requirements. The code sm stands for medium compressibility, sh for increased and sg for low compressibility.
Impact sound insulation lies under the screed and forms the spring of the floating floor. An acoustic underlay lies directly beneath laminate or parquet and mainly improves the floor covering. It does not replace impact sound insulation under the screed.
That depends on the product and the build-up. Dynamic stiffness is more important than thickness. Standard insulation boards under wet screed have a delivered thickness of a few centimetres, while thinner boards with higher compressive strength are often used under dry screed, as specified by the manufacturer.
No. Dry screed systems generally need insulation layers with low compressibility so that boards and joints do not give way. The dry screed manufacturer specifies which insulation is permitted.
Sources
- DIN 4108-10:2021-11 Thermal insulation and energy economy in buildings, Part 10: Application-related requirements for thermal insulation materials, factory-made products. DIN Media.
- DIN EN 29052-1:1992-08 Determination of dynamic stiffness, Part 1: Materials used under floating floors in dwellings. DIN Media.
- DIN EN ISO 10140-3 Laboratory measurement of sound insulation of building elements, Part 3: Measurement of impact sound insulation. DIN Media.
- DIN EN ISO 717-2:2021-05 Rating of sound insulation in buildings and of building elements, Part 2: Impact sound insulation. DIN Media.
- EPLF: Technical leaflet on underlay materials for laminate flooring, edition 12/2022.
- Schröder: Mitteilung 439, Fraunhofer Institute for Building Physics, 2004.
- Wolf Bavaria: PowerFloor product page with tested floor build-ups.